SPLIT-CORE installation does not require the load conductor to be disconnected.
SOLID-CORE installation requires the load conductor to be disconnected in order to "thread" through the center of the CT.
CT installation inside the electrical panel must be done by a qualified individual or electrician. This individual must be knowledgeable and obey all safety procedures and local electrical code. See users manual for more safety information.
Make sure your service is not 3-phase or powered from two phases of a 3-phase source. The ECM-1240 is designed for 120V/240V split-phase systems only.
The Micro-40 CT is used primarily for panel circuits up to 40A. If aluminum wiring is used, the limit for this CT may be 20A due to the larger diameter/A of aluminum.
RULES
Up to 5 Micro-40 CTs per channel as long as the total amperage of all CTs does not exceed 80A.
Cannot be combined with other CT models when connected to a given channel.
Mostly used with AUX channels but may be used with CH1 or CH2.
ADVANTAGE
Low Cost
Extremely small size uses minimal panel space.
More than two CTmay be used on a given channel
DISADVANTAGE
Lower accuracy
Installation requires turning the power off and disconnection of conductor to allow threading the conductor through the center of the CT.
The Micro-80 CT is used primarily for panel circuits up to 80A.
RULES
Up to 5 Micro-80 CTs per channel as long as the total amperage of all CTs does not exceed 80A. The maximum amperage may be extended to 160A using a special configuration.
Cannot be combined with other CT models when connected to a given channel.
Mostly used with AUX channels but may be used with CH1 or CH2.
ADVANTAGE
Low Cost
Small size uses minimal panel space.
More than two CTmay be used on a given channel
DISADVANTAGE
Lower accuracy
Installation requires turning the power off and disconnection of conductor to allow threading the conductor through the center of the CT.
The SPLIT-170 CT is used in situations where the main panel uses rectangular buss bars instead of typical round conductors. (See example picture). The rectangular shape of this CT accomodates the buss bar where the SPLIT-200 CT would not.