How The ECM-1220 Derives True Power
A brief explanation of how the ECM-1220 compiles the
power used by a load will make it much easier to understand how to
connect it and interpret the readings.
In order to meter true power, the load's current and
voltage must be sampled. This must be performed in real time because
something called "power factor" comes into play.
The ECM-1220 does this by sampling the current via
current transformer (CT), and the voltage from the wall transformer,
which is proportional to the line voltage. See diagram below.

Figure 1
One of the ECM-1220 settings is "PT Setting". This
setting tells the ECM-1220 what secondary voltage coincides with 120V on
the primary side. This value is preset at the factory and should only
require changing for certain connection types. These values could be
read from a label on the wall transformer.
The same principle applies to the "CT Setting". The
ECM-1220 needs to be set to a value representing the appropriate current
ratio of the current transformer.
Based on the diagram above, the channel in which the
CT is plugged into will provide the power for that load.
Referring to figure 2, the load is connected to the
opposite phase. Assuming the same load as that in figure1, the ECM-1220
will display the same power.

Figure 2
This setup may produce a slight error if Line1(black)
voltage differs from Line2 voltage (red). This error is usually
negligible since service panels are generally fairly balanced.
The technique used by the ECM-1220 when monitoring
240V loads is a combination of both figure1 and fugure 2. This technique
is shown in figure3.

Figure 3
As you can see, an additional current transformer is
used so that each line may be monitored by each channel. The total power
for this load is then the sum of each channel.
There has been some confusion with this type of
setup because a 240V load is monitored and 120V is displayed.
Essentially, the same 120V is used to calculate the power of each
channel.
Monitoring a 240V load using this method has the
advantage of viewing the power of each half of the load separately. This
is beneficial in determining how balanced the load is. For some loads,
this provides greater insight, such as a clothes dryer with a 240V
heating element and a 120V motor. The heating and motor power may then
be calculated separately.
Examples of figure 1 and figure 3 may be all you will
ever require for most applications. The next section will describe some
variations of the above and techniques for simpler and more
complex application.
Connecting the ECM-1220 to Various
Load Types
Please Note:
All examples below are based on 60Hz
frequency. The ECM-1220 currently is not compatible with 50Hz systems.
Any installation which requires work
inside service panels, junction boxes or other areas with live
conductors should only be performed by a qualified individual having
knowledge of the dangers involved, using proper safety practices and
obeying all local electrical codes.
The example in figure 3 shows how to
connect to a 3-wire 120V/240V load (Line1,Line2 and Neutral). Some 240V
loads only use two wires, line1, line2 and no neutral. One such example is
an electric baseboard heater.

Figure 4
You may simply use the same technique based on that
of figure 3 (redrawn in figure 4), or you may prefer to monitor with
only one CT, since the same current flows through line1 and line2 as
shown in figure 5.

Figure 5
The setup in figure 5 allows the load to be monitored
with only one CT using only one channel, allowing a second similar load
to be monitored with the second channel.
There is one important difference to note in this
example:
In figure 4, both channels were used, deriving the
power for both halves of the 240V load and the power was the sum of both
halves.
In figure 5, only one channel is used to derive the
total power, therefore the load is treated like the basic example of
figure 1, only now the ECM-1220 needs to assume a voltage of 240V, the
actual load voltage.
This is simply done by changing the PT Range from "3"
to "2". This double the voltage value. The ECM-1220 will now display
240V, although powered by a 120V receptacle. The displayed power will
represent the actual load power.
This method should only be used for applications
where the load does not make use of the neutral connection.
You may run into a situation where you need to
monitor a 240V load without having access to 120V. Figure 6 shows how to
connect for this situation.

Figure 6
Since the ECM-1220's wall transformer may NOT be
connected directly to 240V, Brultech has 240V:120V step down transformer
available to use for this application. Once again, the ECM-1220 needs to
know that you are monitoring a load connected to 240V. Therefore you
will need to double the PT range by setting it to "2".
There is one important difference this time around!
The step-down transformer does not provide a perfect 2:1 reduction
ratio. This is easily compensated by adjusting the CT type. This value
is supplied with the transformer if purchasing this option.
Under Construction
..... more examples coming